Experimental equipment for determining the effectiveness of the cold in refrigeration systems

Scientific domain

PE11: Materials Engineering


Keywords

Effectiveness of the cold in refrigeration systems


Home partner institution

University of Oradea


Technical staff available No
Remote access details No
Remote access available No
Open to external users No
Equipment Experimental equipment for determining the effectiveness of the cold in refrigeration systems
Open access to updated information database No
Online booking system details No
Online booking system available No
Description Equipment ID : 22. Type : equipment, year of purchase : 2015, university ID : 7. Technical Data 3 compressors - refrigeration capacity: each 1584W at -10°C/55°C - power consumption: each 1156W at -10°C/55°C Condenser with fan - capacity: 4100W - volumetric air flow rate: 1250m³/h Coaxial coil heat exchanger capacity - 4kW at ΔT=9K; 0,6m³/h glycol-water mixture Glycol-water mixture pump - max. flow rate: 4,2m³/h - max. head: 5,6m Heater power: 3kW Tank - glycol-water mixture: 23L - refrigeration circuit receiver: 5,8L Measuring ranges - temperature: 4x 0...100°C, 4x -100°C...100°C - pressure: 1x -1...9bar, 1x -1...24bar - flow rate: 1x 1...25L/min - compressor power: 0...4995W